01Process
MV dead time 0.25Select an instrument or the steam valve to see what it does.
02Time Response
Try adjusting the steam valve in manual mode.
03PID Controller
MAN- MV · Valve
- 60.0%
- PV · Measured
- 75.0%
- SP · Setpoint
- 50.0%
Select the faceplate to switch MAN / AUTO.
Tuning & Control Options
Lab Exercises & Process Model
Three Experiments
- Open-loop response: Run the MV step. The steam valve opening changes from 40% to 65%. Compare how long it takes PV to respond at each process difficulty.
- Closed-loop response: Select the SP step and set 1/Ti and Td to zero for P-only control. Select Freeze Plot, set 1/Ti to 1.5, and run the same step to compare the PI response.
- Disturbance rejection: Compare the open-loop and closed-loop DV steps. Does PV return to its setpoint? Then try changing the anti-reset windup and kick prevention options.
Scaling and Dynamics
The plot uses normalized time from 0 to 10 and displays signals in percent. For PV and SP, temperature (°C) = 18 + 0.7 × signal (%). For DV, feed temperature (°C) = 13 + 0.1 × DV (%). Heat duty (kW) = 0.8 × MV (%).
The process has two first-order lags with time constants of 1 and 0.5. MV dead time is 0.05 (Easy), 0.25 (Normal), or 0.75 (Hard). DV dead time is 0.10. These values use the original normalized time scale.
Anti-reset windup also limits MV to 0–100%. With No proportional kick enabled, the proportional term uses the baseline SP of 50%, as in the original applet.