AI-Based Process Dynamics and Control - Module 1: PID Controller

Control the outlet temperature of a steam-jacketed stirred tank.

01Process

MV dead time 0.25
Steam-jacketed stirred tank and temperature control loop. Select an instrument to learn what it does. Jacketed tank Feed · DV (°C) Outlet · PV (°C) Steam · MV (kW) Condensate 18.0 70.5 48.0
PV · Outlet temp.70.5 °C
MV · Heat duty48.0 kW

Select an instrument or the steam valve to see what it does.

02Time Response

PV · Outlet temp. SP · Setpoint MV · Steam valve
Select Run to plot the response.
READY · 0.00 / 10

Try adjusting the steam valve in manual mode.

03PID Controller

MAN
MV · Valve
60.0%
PV · Measured
75.0%
SP · Setpoint
50.0%

Select the faceplate to switch MAN / AUTO.

Tuning & Control Options
Lab Exercises & Process Model

Three Experiments

  1. Open-loop response: Run the MV step. The steam valve opening changes from 40% to 65%. Compare how long it takes PV to respond at each process difficulty.
  2. Closed-loop response: Select the SP step and set 1/Ti and Td to zero for P-only control. Select Freeze Plot, set 1/Ti to 1.5, and run the same step to compare the PI response.
  3. Disturbance rejection: Compare the open-loop and closed-loop DV steps. Does PV return to its setpoint? Then try changing the anti-reset windup and kick prevention options.

Scaling and Dynamics

The plot uses normalized time from 0 to 10 and displays signals in percent. For PV and SP, temperature (°C) = 18 + 0.7 × signal (%). For DV, feed temperature (°C) = 13 + 0.1 × DV (%). Heat duty (kW) = 0.8 × MV (%).

The process has two first-order lags with time constants of 1 and 0.5. MV dead time is 0.05 (Easy), 0.25 (Normal), or 0.75 (Hard). DV dead time is 0.10. These values use the original normalized time scale.

Anti-reset windup also limits MV to 0–100%. With No proportional kick enabled, the proportional term uses the baseline SP of 50%, as in the original applet.