← ECML Hub

AI-Based Process Dynamics and Control - Module 2: DP Cell

Measure flow with an orifice plate and a differential pressure transmitter.

01Measurement Loop

LIVE
Orifice plate, differential pressure transmitter, and the 250 ohm resistor in the measurement loop 50.00 250.00 % L/min
Fitted orificeSelect a marker or readout to inspect its instrument.
Actual Flow250.00 L/min
Final Reading250.00 L/min

Measurement error: 0.00 L/min

02Signal Chain

Select an instrument to inspect its range and adjust its calibration.

03Strip Chart

×1
Actual flow Raw signal Final reading

Raw signal uses the nominal 1–5 V to 0–500 L/min scale. At ×2 and above, each zoom change centers the vertical scale on the current actual flow.

04Instrument Settings

Orifice Plate

Meter viewing scale

Lab Exercises & Measurement Model

Three Experiments

  1. Calibration: Use the fitted orifice with noise and filtering set to None. Try several flow rates and compare actual flow with the final reading. Select DP Cell and turn off square-root extraction to see how the response changes.
  2. Orifice sizing: At 500 L/min, compare the smaller and larger orifices. Check which instrument first reaches its limit. Try adjusting the DP Cell span to calibrate the larger orifice.
  3. Noise and lag: Add process noise and compare the raw signal with the final reading. Select a heavier filter, then change actual flow. Compare the noise reduction with the time it takes the reading to settle.

From Differential Pressure to Flow

The orifice produces ΔP = (Q/C)2. The DP cell maps its input range to 4–20 mA. With the fitted orifice and default calibration, square-root extraction makes current proportional to flow.

The I/V converter maps 4–20 mA to 1–5 V. The first-order filter samples every 0.25 s. A larger time constant smooths noise and slows the response to a flow change.

In linear mode, Zero maps to the lower output limit and Span is the input interval. Square-root extraction follows the applet formula (√ΔP − √Zero) / √Span before scaling to 4–20 mA. Meter viewing scales affect the display only.