01Valve Installation
02Valve Characteristics
INSTALLEDTarget travel: 50.0%. The positioner tracks the command.
03Flow Control Settings
Full-open flow: 221.9 gpm
Below the 250.0 gpm target.
Lab Exercises & Valve Model
Three Experiments
- Inherent characteristic: Select Inherent and sweep the command from 4 to 20 mA. Compare the three trims. Change R and observe how it reshapes the Equal Percentage curve.
- Installed characteristic and sizing: Select Installed. Change the reference pressure loss and compare the curves. Set a desired flow and adjust rated Cv to see whether the valve can reach it.
- Hysteresis: With Air-to-Open selected, set the command to 12 mA, select Hysteresis, and make small changes in both directions. Watch target travel and actual opening, then switch to Positioner.
From Command Signal to Flow
The I/P transducer maps 4–20 mA to 3–15 psig. More air opens an Air-to-Open valve and closes an Air-to-Close valve.
For fractional opening x, the original trim factors are x, √x, and Rx−1. The Equal Percentage curve retains its modeled minimum Cv/R at zero travel.
Installed mode splits pump pressure between the valve and the process. Process ΔP = reference ΔP × (flow / reference flow)2. Inherent mode sets process ΔP to zero, so the valve sees a constant pressure drop.
Hysteresis follows the applet's simplified deadband model. The positioner makes the stem track target travel.